Sale!

DEIF MTR-4-215 | RS485 Modbus Network Transducer, In Stock

Original price was: ¥999.00.Current price is: ¥888.00.

DEIF MTR-4-215 | RS485 Modbus Network Transducer, In Stock

  • Model: DEIF MTR-4-215
  • Brand: DEIF
  • Series: MTR-4 Series
  • Function: Measures and monitors single-phase or three-phase electrical power networks, providing calculated network values via analogue outputs and digital communications.
  • Product Type: Multi-Function Power Transducer
  • Core Specs: 2 Analogue Outputs | RS-485 Modbus RTU | Universal Power Supply (19-300V DC / 40-276V AC)
  • Condition: New Surplus
Category:

Description

DEIF MTR-4-215 | RS485 Modbus Network Transducer, In Stock

 

Architect’s Product Breakdown

The DEIF MTR-4-215 operates as a high-precision multi-transducer designed to sample voltage and current inputs rapidly from single-phase or complex three-phase industrial and marine power networks. Within switchboard and control panel architectures, this specific model processes over 50 electrical parameters through fast sampling, converting raw AC waveforms into reliable analogue signals and digital Modbus registers without external transducer stacking.

Integrating this hardware into switchgear enclosures requires careful attention to terminal torque, signal shielding, and network termination. Because the unit accepts a wide range of auxiliary voltages and processes high-voltage inputs directly from potential transformers (PTs) and current transformers (CTs), physical separation between high-energy power wiring and low-voltage communication loops is mandatory to prevent electromagnetic interference from corrupting serial data streams or analogue scaling loops.

MTR-4-215

MTR-4-215

Key Technical Specifications

Parameter Specification
Manufacturer DEIF
Model Designation MTR-4-215
Network Topologies 1-phase, 3-phase balanced/unbalanced, 3- or 4-wire systems
Auxiliary Power Supply 19 to 300 V DC / 40 to 276 V AC (Universal)
Analogue Outputs 2 configurable outputs (mA or V)
Communication Interface RS-485 Modbus RTU (up to 115,200 bit/s)
Accuracy Class Class 0.5 / 0.4 for power/energy, 0.2 for voltage/current
Mounting Style 35 mm DIN Rail
Ambient Operating Temperature -10°C to 55°C
Enclosure Protection IP20 housing, IP40 front

 

Field Engineer’s Pitfall Guide

  • WARNING: CT Open-Circuit Hazard. Never disconnect secondary wiring from current transformers feeding the MTR-4-215 while the primary power circuit is energized. Opening a live CT secondary will generate lethal high-voltage spikes and destroy internal input stages.
  • WARNING: RS-485 Polarity and Biasing. Ensure correct polarity on the two-wire RS-485 Modbus network and verify proper line termination resistors. Reversing data lines or omitting bias resistors will cause intermittent packet drops across the supervisory control system.
  • WARNING: Auxiliary Voltage Over-Range Transients. Although the unit features a wide power supply window, unsuppressed switching surges on plant auxiliary rails can trigger internal resets; install appropriate transient voltage suppressors on dirty power feeds.

 

QA & Testing SOP

  • Visual & Origin Verification: Inspect the molded housing for structural damage, verify factory terminal markings, and ensure front LED status indicators are unblemished.
  • Auxiliary Power-Up Test: Apply a stable low-voltage DC source to the auxiliary terminals of the model to confirm proper processor boot sequence and watchdog LED flashing.
  • CT/VT Input Calibration Injection: Inject calibrated current and voltage signals into the measurement channels using a precision source to verify accuracy across voltage and current ranges.
  • Communication and Output Verification: Poll internal registers via the RS-485 Modbus port and measure the two analogue output loops with a digital multimeter to confirm scaling linearity.
  • Packaging: Seal in an anti-static moisture-barrier bag and pack with high-density foam cushioning inside a heavy-duty container.

 

Technical FAQ

Can I configure the analogue output scaling without connecting an auxiliary power supply?

Yes. Modern variants of this model support USB configuration directly from a PC interface without requiring auxiliary AC or DC power applied to the unit terminals.

What is the maximum baud rate supported by the RS-485 communication port?

The RS-485 Modbus RTU interface supports selectable baud rates ranging from 2,400 up to 115,200 bit/s.

Does the MTR-4-215 support direct connection to high-voltage networks?

Direct voltage inputs are rated up to specific limits; for systems exceeding standard low-voltage thresholds, external potential transformers (PTs) must be wired to step down inputs to match the hardware ratings.

What precautions are necessary when replacing an older MTR-3 unit with this model?

Ensure that the physical terminal mapping and Modbus register register maps are verified against engineering drawings, as pin assignments and scaling protocols may differ between legacy generations and the current hardware architecture.

Business Card