Sale!

Phoenix Contact PLC-RSC-24UC/21 | Relay Module, New Surplus

Original price was: ¥999.00.Current price is: ¥888.00.

Phoenix Contact PLC-RSC-24UC/21 | Relay Module, New Surplus

  • Model: PLC-RSC-24UC/21 (Part No: 2966184)
  • Brand: Phoenix Contact
  • Series: PLC-INTERFACE System
  • Function: This 6.2mm electromechanical relay module isolates control signals and switches field loads up to 6A using universal AC/DC coil voltage.
  • Product Type: Plug-in Relay Module with Screw Terminal Base
  • Core Specs: 24V AC/DC Input Coil | 1 PDT (SPDT) Contact | 6A Switching Current Rating (Condition: Active Production / Standard Industrial Stock)
Category:

Description

Phoenix Contact PLC-RSC-24UC/21 | Relay Module, New Surplus

 

Architect’s Product Breakdown

The Phoenix Contact PLC-RSC-24UC/21 (Part Number 2966184) functions as an ultra-slim, 6.2mm electromechanical interface relay designed for heavy-duty industrial automation applications. Combining a screw-connection terminal base with a plug-in miniature power relay, this unit delivers galvanic isolation between sensitive PLC input/output cards and noisy field actuators or sensors. The universal coil circuit accepts both 24V AC and 24V DC input signals without external adaptation, simplifying parts inventory across mixed-signal control panels.

Integrating this assembly into control cabinets eliminates the space penalties typically associated with traditional interposing relays. Plug-in bridging bars (FBST series) can link power supplies across multiple adjacent bases, drastically cutting down internal cabinet wiring labor. When a relay eventually reaches its mechanical wear limit, the integrated plastic retaining and ejector lever allows technicians to swap out the plug-in switching element in seconds without disconnecting any field wiring from the base terminal block.

PLC-RSC-24UC

PLC-RSC-24UC

Key Technical Specifications

  • Manufacturer Part Number: 2966184
  • Model Designation: PLC-RSC-24UC/21
  • Nominal Input Voltage (U_N): 24V AC/DC (50/60 Hz)
  • Typical Input Current: 11 mA
  • Contact Type: 1 PDT (Single Pole Double Throw / Changeover contact)
  • Contact Material: AgSnO (Silver Tin Oxide) for standard power switching
  • Max Switching Voltage: 250V AC/DC
  • Limiting Continuous Current: 6A
  • Connection Technology: Screw Connection (26 to 14 AWG)
  • Housing Width: 6.2 mm ultra-compact profile
  • Operating Temperature Range: -40°C to +60°C

 

Field Engineer’s Pitfall Guide (Unique Value)

  • Warning: Mismatching Contact Material for Low-Energy Signals. Using the standard silver tin oxide (AgSnO) contacts of the PLC-RSC-24UC/21 to switch low-level PLC analog or pulse signals (< 5V, < 10mA) will cause an insulating oxide layer to form over time, resulting in erratic signal readings. Use the gold-plated contact variant (suffix /21AU) for dry circuit or low-energy telemetry switching.
  • Warning: Overlooking AC Inductive Kickback. When driving high-inductive loads like small AC solenoids or contactors, failing to add external RC snubbers or freewheeling suppression across the load will prematurely pit and weld the relay contacts shut.
  • Warning: Overtightening Terminal Screws. The M3 clamping screws on these 6.2mm bases demand a controlled torque of 0.6 Nm to 0.8 Nm. Excessive torque snaps the internal terminal cage and wrecks the housing block.

 

QA & Testing SOP (Transparency)

  • Visual & Structural Check: Verification of housing integrity, screw terminal thread smoothness, and insertion pin straightness.
  • Coil Voltage Response Test: Applied 24V AC and 24V DC independently to terminals A1/A2 to confirm reliable relay pickup and dropout thresholds.
  • Contact Resistance & Switching Verification: Automated continuity testing across common (11), normally open (14), and normally closed (12) contacts under simulated load.
  • LED Status Validation: Inspection of internal green status indicator illumination during coil energization.
  • Anti-Static Packaging: Sealed in industrial protective bagging prior to dispatch.

 

Technical FAQ

  • Can the plug-in relay be replaced without removing the base terminal block? Yes. The integrated plastic lever unlatches and ejects the plug-in relay directly from the socket while all field wiring remains securely attached to the screw terminals.
  • What is the difference between PLC-RSC-24UC/21 and PLC-RSC-24DC/21? The /24UC model accepts both AC and DC 24V signals on its coil, whereas the /24DC variant is strictly limited to 24V DC input coils.
  • Can I bridge the power supply across multiple relay modules? Yes. Plug-in pluggable bridge combs (such as FBST 500-PLC) insert into the upper bus slots of adjacent modules to distribute 24V power rapidly without jumper wires.
  • Is this module rated for hazardous locations? Standard commercial stock is rated for general industrial environments; specific ATEX/IECEx certified variants must be specified if installed inside Class I, Div 2 hazardous zones.
Business Card